1.Check all trunkings are properly covered                      

检查所有线槽都全封盖                           

2. Check cable entry to box is wellterminated                         

检查进入配电箱的电览收尾良好                           

3. Check all wall openings are fully sealedwith fire                          

   resistance materials                          

检查过墙洞囗填塞以防火材料                      

4.Check floor openings is fully sealed withfire resistance                        

  materials                     

检查地面洞囗填充以防火材料                      

5.Check all cables are correctly tied toladder                          

检查所有电览正确地扣在览架上                           

6.Check all distribution boxes top port areproperly sealed                     

检查配电箱上方开口适当密封                      

7.Check all electrical boxes are correctlyearthed                   

检查配电箱正确地                           

8.Check earth bar inside ditribution boxsufficient                   

  for all earth lines                          

检查配电箱接地桥尺寸足够供所有地线                       

9.Check all earth lines inside distributionboxes are                        

  tightly secured                    

检查配电箱接地线在接桥己旋紧                           

10.Check all circuit breakers wiring areproper termination                    

    and tightly secured                          

检查所有空开的电线已旋紧及良好收尾                      

11.Check circuit breakers tripping current arecorrectly set                   

检查各接触器跳闸保护设置正确                           

12.Check cable number marking is wrappedfor all cabling                      

检查线览标签套在线缆上                      

13.Check colour marking is correctly markedon cables                  

检查电缆上的相位颜色标签正确                           

14.Circuit breaker box is securely earthed                       

检查接触器盒接地旋紧                           

15.All cables are clearely labelled &inlined with room no.                      

所有电线标号与房号相符                      

16.Check BMS lighting control box isproperly set up.                      

检查楼宇自控灯光控制箱设置适当                      

17.Check room lighting is provided andworkable                    

检查房内已提供照度灯及可以工作                      

18.Check fire detector is provided                    

检查消防检测器己安装                           

19.Check switch room door is of fire ratedtype                       

检查电制门为耐火门等级                      

20 Check room door lock for functioning                           

检查门锁工作正常

平台

本站仅提供存储服务,所有内容均由用户发布,如发现有害或侵权内容,请点击举报
打开APP,阅读全文并永久保存 查看更多类似文章
猜你喜欢
类似文章
【热】打开小程序,算一算2024你的财运
中级:医院门诊——Hospital and Clinics
副机吊缸参数测量
听力信息必备词汇
Common domestic electric cable types used in ...
酒店服务
机场迷路?机场常见指示牌中英文对照
更多类似文章 >>
生活服务
热点新闻
分享 收藏 导长图 关注 下载文章
绑定账号成功
后续可登录账号畅享VIP特权!
如果VIP功能使用有故障,
可点击这里联系客服!

联系客服